The Linear Thermal Detector (LTD) is a twin conductor cable with a heat-sensitive covering protected by an outer sheath. In a fire or overheat condition, the heat sensitive covering melts, causing the conductors to short, which alarms the system.
Continuous detection over complete length of sensor
Simple assembly using suitable fixings (e.g. cable ties or P clamps)
LTD spacers protect against damage
Continuous line monitoring using Kidde end of line connector
Provides alarm signal to Kidde controllers
Activation occurs when the temperature-sensitive insulation on the two internal wires melt shorting the wires together. Detector is routed within hazard area.
PRODUCT SPECIFICATIONS
Minimum bend radius
3 in./75mm
Nominal current draw
0mA
Alarm temperature
350°F/177°C
Operating temperature
221°F/105°C
Note: If the wire alarms to a fire, the wire must be replaced prior to returning the system to service.